Description
FC-102P2K2T4E20H2XGXXXXSXXXXAGBKCXXXXD0
Frequency Converter
FC-102P2K2T4E20H2XGXXXXSXXXXAGBKCXXXXD0
VLT® HVAC Drive FC-102
(P2K2) 2.2 KW / 3.0 HP, Three phase
380 – 480 VAC, (E20) IP20 / Chassis
RFI Filter
No brake chopper
Graphical Loc. Cont. Panel
Not coated PCB, No Mains Option
Latest release std. SW.
LonWorks MCA 108, MCB-101 General purp. I/O
No C1 option, MCB-107 24V DC backup
Frame: A2
Other options according to Model code
Model code :
FC-102P2K2T4E20H2XGXXXXSXXXXAGBKCXXXXD0
Danfoss Drive is dedicated to ventilation, heating, and refrigeration applications. With a wide range of powerful sta.
Gross weight | 5.2 kg |
Net weight | 4.9 kg |
Volume | 16.53 l |
EAN | 5702427174863 |
VLT® HVAC DRIVE FC 100 SERIES
Product View (Switch) | GLBL | Global (Standard) |
Product Group | FC- | VLT® HVAC Drive FC- |
Series | 102 | 102 |
Power Rating | P2K2 | (P2K2) 2.2 KW / 3.0 HP |
Phase | T | Three phase |
Mains Voltage | 4 | 380 – 480 VAC |
Enclosure | E20 | (E20) IP20 / Chassis |
RFI Filter | H2 | RFI Filter |
Brake – Safe Stop | X | No brake chopper |
LCP | G | Graphical Loc. Cont. Panel |
Coating PCB | X | Not coated PCB |
Mains Option | X | No Mains Option |
Adaptation A | X | Standard Cable Entries |
Adaptation B | X | No adaptation |
Software Release | SXXX | Latest release std. SW. |
Software Language Pack | X | Standard Language Pack |
A Option | AG | LonWorks MCA 108 |
B Option | BK | MCB-101 General purp. I/O |
C0 Option MCO | CX | No C0 option |
C1 Option | X | No C1 option |
C Option Software | XX | No software option |
D Option | D0 | MCB-107 24V DC backup |
Frame Size | A2 | A2 |
Product Catalog | NO_VIEW | NO VIEW |
Typecode Part 1 | FC-102P2K2T4E20H2XGX | |
Typecode Part 2 | XXXSXXXXAGBKCXXXXD0 | |
Power 110% (NO) [KW] | 2.2 | |
Height [mm] | 268,0 | |
Width w/ no C options [mm] | 90,0 | |
Depth [mm] | 205,0 | |
Depth with Option A/B [mm] | 220,0 | |
kVA | 3.88 | |
Power Loss NO [W] | 88 | |
Power Loss NO [W] | 88 | |
Continuous Current (NO) [A] | 5.6 | |
Intermittent Current (NO) [A] | 6.16 | |
Continuous Current (NO) [A] | 4.8 | |
Intermittent Current (NO) [A] | 5.28 | |
Calculated Gross Weight [kg] | 5.1 | |
Calculated Net Weight [kg] | 4.8 | |
Material Gross Weight | 5.2 | |
Material Net Weight | 4.9 | |
Vendor | ERR01 | Cannot Determine Vendor |
Recommended Factory | ERR01 | Cannot Determine Vendor |
Modelcode01 | FC-102P2K2T4E20H2XGX | |
Modelcode02 | XXXSXXXXAGBKCXXXXD0 |